Ravel 8 Zone Fire Alarm system
Ravel 8 Zone Fire Alarm system
- Product Code : Ravel 8 Zone Fire Alarm system
- Availability : In Stock
-
₹ 18,990.00
- Ex Tax :₹ 18,990.00
Product Overview
RE-2558 is an UL Listed Microprocessor based conventional Fire Alarm Control Panel which has 8 Zones . These control panels are designed to be used in small and medium sized commercial complexes, buildings, hotels, schools, and industrial establishments. They are compatible with conventional detectors, manual call points and normally open dry contact devices.
Special Features
- Switched Mode Power Supply.
- Modular Construction
- Auto Resettable Fuse
- Surge Protection for all Input and outputs.
- Programmable AC loss delay/Trouble Remainder/Alarm Verification
- Battery polarity reversible protection
- Surface Mount Technology
- Over All current consumption is low.
Features
- Fully complies with UL -864 and NFPA-72.
- Rugged CRCA sheet with powder coated finish.
- Operates on 110 - 220VAC, 50 /60 Hz, AC mains power supply.
- 16x2 dot matrix LCD display.
- 4/8 Class B Style ‘B ‘ or Style ’C’ initiating device circuit (IDC).
- All zones accept smoke detectors and normal open contact devices.
- Any zone can be configured as alarm or supervisory zone.
- 2 Class B notification appliance circuits (NAC).
- NAC shall be programmed as silenceable or non- Silenceable.
- Supervisory zone shall be latching or resettable.
- Standby (battery) backup 24VDC power supply with built in charger
- Error free Fire / Fault status in unambiguous colored LED indication.
- System ON indication.
- Main & Standby status with audible and visual indication.
- Battery low visual warning with audible tone.
- FormC relays for fire, fault and supervisory.
- Resettable / Steady 24VDC Output.
- RS 485 Communication facility (Optional).
- Lamp test facility.
- All field wiring circuits are power limited except 110 - 220VAC and battery.
- All field wiring circuits are supervised.
- Walk test facility.
- Zone Isolation facility with loop voltage cut off.
- Earth fault annunciation facility at 0 ohms.
- AC low voltage cutoff.
- Programmable AC loss delay.
- Programmable alarm verification.
- Programmable trouble reminder.
Electrical Specification
Primary Power
110 - 220VAC ± 10%, 50 Hz, 100W.
Standby Power
24VDC (2 Nos of 12V, 12Ah Sealed Lead acid battery).
Quiescent current : 120mA
Operating Condition
Operating Temperature : 0 - 49° C/32-120° F.
Storage Temperature 0 C to 60 C
Relative Humidity : 93 ± 2% RH (noncondensing) at 32 ±2° C/90 ±3° F.
Charging Circuit
Charging Voltage : 28.0V, ±2%
Charging Current : 800mA (Max.).
Notification Appliance Circuits
Class B Style - Y wiring Operating Nominal Voltage | 24VDC |
Current for all NACs | 1.2Amps (0.6A per circuit) |
Line Drop | 1.8V |
End-Of-Line Resistor | 3K9, 1/2watt |
Common Relays
Type | Form C |
No of Relays | 3 |
Relay Contact Rating | 2Amps @ 30 VDC, 0.5Amps @125VAC. |
Power Factor | 1.0 |
Initiating Device Circuits (Zone Circuit)
All zones are Class B wiring Normal Operating Voltage | 14- 21 VDC |
Alarm Current | 15 - 30 mA |
Short Circuit Current | 45 mA Maximum |
Loop resistance | 100 ohms Maximum |
End-Of-Line Resistor | 3K9, 1/2 watt |
Standby Current | 7 mA (2 mA for Detectors) |
Mounting Details
Mechanical Specification
Dimensions | (350W X 250H X 100D) |
Color | Red / White |
Construction | 18 Gauge (1.22mm) CRCA sheet with powder-coated Finish |
IP Rating | IP50 |
Cable Entry | 11xø19mm Knockout in top of the cabinet |
Wiring Diagram
Ordering Information:
MODEL | DESCRIPTION |
RE-104-W | 4 ZONE Fire Alarm Panel |
RE-104-R | 4 ZONE Fire Alarm Panel |
Compatible Devices
MODEL | DESCRIPTION |
RE-316S-2L | Photoelectric Smoke detector with base. |
RE-316H-2L | Heat detector with base. |
RE-316SH-2L | Photoelectric & Heat detector with base |
RE-716 MR | Conventional Manual Call Point. |
RE- 24 CS | Conventional Sounder. |